Answer Posted / chetan
KVAR Required is
KVAR = P [tan (phi 1) - tan (phi 2) ]
where P = total KW
phi 1 = angle corresponds to power factor to be improved . ie cos ph 1 = 0.9
phi 2 = angle corresponds to power factor given . ie cos ph 2 = 0.7
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
Is it posible to instal one more SMDB from the existing SMDB and is it practical.
how can we determine size of a cable by knowing the kw or current rating of a load?how can we calculate the resistance box of a slip ring motor?
Explain how you decide what size of electrical wire do you need?
i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester
why is using sensor?what is differece between photoelectric and proxmitty?
before transformer oil dielectric strenght tests are taken the oil should be allowed to settle to remove option 1 air bubbles 2 gasses 3 contamination 4 water
How to Calculate Current Rating of SDFU (Switch Disconnector Fuse unit) for Protectionof Capacitor Bank connected to Busbar of 800Amp,in LV side of 11/0.433KV, 250KVA Transformer?
tan delta equation test on alternators
What is the Minimum winding resistance of motors ( small & big)? referance range
if the armature current in a dc generator is ac ( sinusoidal ) why doesnt the sjhape af armature mmf a sinusoidal (ni) ? armature mmf in case of a dc machine is triangular.
Refernce currents are to be generated using refernce cueernts how can this be done??
What is MSL designation of a motor and same may be provided in details.
Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?
what is the difference between transformer,converter and transducer
list the advantages of RCCB over other circuit breakers?