Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Simple calculation of improving power factor?

Answer Posted / chetan

KVAR Required is

KVAR = P [tan (phi 1) - tan (phi 2) ]

where P = total KW
phi 1 = angle corresponds to power factor to be improved . ie cos ph 1 = 0.9

phi 2 = angle corresponds to power factor given . ie cos ph 2 = 0.7

Is This Answer Correct ?    7 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is it posible to instal one more SMDB from the existing SMDB and is it practical.

2099


how can we determine size of a cable by knowing the kw or current rating of a load?how can we calculate the resistance box of a slip ring motor?

1776


Explain how you decide what size of electrical wire do you need?

1141


i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester

2167


why is using sensor?what is differece between photoelectric and proxmitty?

2012


before transformer oil dielectric strenght tests are taken the oil should be allowed to settle to remove option 1 air bubbles 2 gasses 3 contamination 4 water

1667


How to Calculate Current Rating of SDFU (Switch Disconnector Fuse unit) for Protectionof Capacitor Bank connected to Busbar of 800Amp,in LV side of 11/0.433KV, 250KVA Transformer?

5401


tan delta equation test on alternators

2225


What is the Minimum winding resistance of motors ( small & big)? referance range

2317


if the armature current in a dc generator is ac ( sinusoidal ) why doesnt the sjhape af armature mmf a sinusoidal (ni) ? armature mmf in case of a dc machine is triangular.

1984


Refernce currents are to be generated using refernce cueernts how can this be done??

2008


What is MSL designation of a motor and same may be provided in details.

1722


Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?

2234


what is the difference between transformer,converter and transducer

1678


list the advantages of RCCB over other circuit breakers?

1711