WHAT ARE THE DFT AND RMS MEASURMENTS PRINCIPLE IN NUMERICAL
TECHNOLOGY OF POWER SYSTEM ?? WHICH IS BETTER IN WHICH
QUANTITY MEASURNMENT??
Answer Posted / otto
RMS
The AC component is the effective mean value of the positive
and negative peak values.
RMS is used in applications where the effect of the DC
component must be taken
into account.
DFT
In the DFT mode, the fundamental frequency component of
the measured signal is numerically calculated from the
samples. In some applications, for example, it can be
difficult to accomplish sufficiently sensitive
settings and accurate operation of the low stage, which may
be due to a considerable amount of harmonics on the primary
side currents. In such a case, the operation can be based
solely on the fundamental frequency component of the
current. In addition, the DFT mode has slightly higher CT
requirements than the peakto-peak mode, if used with high
and instantaneous stages.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
how to determine ct ratio in ht vcb?
why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?
What is the necessary condition for stability.
how to carry out Magnetizing Current Test on Distribution transformer and what purpose we are doing this test. why transformer rating in always in KVA ? what ispositive, negative, zero sequence impedence? How ElCB tripping if Neutral touch with ground Why AC & DC capacitor are use in UPS ? why motor rating in KW? how to syncronize two dg sets
What is the need of generator relay panel
Explain what are inter-poles and why they are required in a dc machine.
What are the different circuits in thermal power plant?
For overhead protection we use which transformer?
defination of lines
Can you tell me more about pu systems (per unit systems )calculation in large power systems? how to get the base for voltage and power in generator, transformator and transmission lines?
State the other types of Air Conditioners?
DG SET BLOCK DIGRAM
What is the principal of motor?
What are the disadvantages of autotransformer?
How to test REF relay testing for LV panel as per Kahramaa standard?