T.x range -0.1 to 0.2 milibar,so how much mili ampear at 0.1 milibar?
Answer Posted / sampath
LRV = -0.1 mbar
URV = 0.2 mbar
SPAN= 0.3 mbar
( 0.2/0.3 )* 16 + 4 = 14.67 mA @ 0.1 mbar
| Is This Answer Correct ? | 11 Yes | 9 No |