how we convert Mili ampere
to temp txt,level txt,flow txt,pressure txt range value
Answer Posted / faiyaz ahmad
Hai Mr. charan kumar,
Actually the formulae is:
Range= (Actual value(mA)- LRV/Span) * 100%
Span=URV-LRV
=20mA-4mA
=16mA
So,Range=(12-4/16)*100%
=(1/2)*100%
=50%
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Explain the burnout feature.
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?
we are having yokogawa centum cs3000 dcs in our power plant. i need some of the operator guides NOT to appear in HIS0163 AND HIS 0162 but it shoul appear in HIS0164 HOW TO DO IT?
Square root calculation for dp flow transmitter?
How to Calibrate Vortex Flow transmitter in field
Explain the use of hair spring in the pressure gauge.
Area classification, Equipments, Gas groups, temperature classification, Ingress protection, Fire Extinguishers.
Why boiler chimney area oxyden sensor fixing?
components of control circuit belongs to control valve
what is the field bus calble ? what are diffrences in orang colur cable and black coular calble ?
what is gas metering system? gas chromatograph? and gas compressors?
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
what is the difference between profibus and controlnet networking.
I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.