Answer Posted / abhishek singh
Core balance CT (CBCT): The CBCT, also known as a zero
sequence CT, is used for earth leakage and earth fault
protection. The concept is similar to the RVT. In the CBCT,
the three core cable or three single cores of a three phase
system pass through the inner diameter of the CT. When the
system is fault free, no current flows in the secondary of
the CBCT. When there is an earth fault, the residual current
(zero phase sequence current) of the system flows through
the secondary of the CBCT and this operates the relay. In
order to design the CBCT, the inner diameter of the CT, the
relay type, the relay setting and the primary operating
current need to be furnished.
| Is This Answer Correct ? | 16 Yes | 3 No |
Post New Answer View All Answers
if any body have question paper of railway (section engineering),then plz send me .i will thank of him/her.
What do you mean by reach and reach the point of the relay?
what is meant by 3rd hormonics ?
what is ramping rate of generator
What is different type of Electrical curve and how it protects the equipment's while up-normal situation?
how to calculate
Draw the wave shape of armature current in a generator subjected to a sudden three phase short- circuit at its terminals. Define various reactance of generator from this wave shape.
Plz tell me how we can find that particular company has vacancy or not
How is the speed of a DC shunt motor related to the armature current?
ult of expression 'document.FrmQF.myem
which type of cabel
HOW TO CALCULATE ELECTRICAL, MECHANICAL,& OVERALL EFICIENCY OF GAS ENGINE POWER PLANT
compare between starting charactristics of synchronous motor with those of 3Q Squirrel cage induction motor
What are the types of excitation system?
Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?