How to take Vector group test of Transformer?
Answer Posted / raj_singh_0376
Procedure of vector group test of transformer
Let’s have a YNd11 transformer.
1) Connect neutral point of star connected winding with earth.
2) Join 1U of HV and 2W of LV together.
3) Apply 415V, three phase supply to HV terminals.
4) Measure voltages between terminals 2U – 1N, 2V – 1N, 2W – 1N, that means voltages between each LV terminal and HV neutral.
5) Also measure voltages between terminals 2V – 1V, 2W – 1W and 2V – 1W.
For YNd11 transformer, we will find,
2U – 1N > 2V – 1N > 2W – 1N
2V – 1W > 2V – 1V or 2W – 1W
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
why the earth is taken minimum in supplying? wather it the proportional factor to getting work any equipment or a power plant?
rajha power sector details
Mention what are the different colors on wires indicates?
what is earthing.how we make it,describe briefly.
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?
Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?
What size cable (based on voltage drop) is required to supply a 40 A three phase boiler if the wiring system is 75V single insulated cables installed in non-metallic rigid conduit 56m from the main switchboard? Voltage drop in the consumer's mains is 8V.
How does HT work & Voltage required?
What is the function of the generator exciter?
Define demand factor?
Explain different types of d.c motors? Give their applications
explain types of electric welding and its applications
when we gave dc supply to 220v dc motor its rpm is 1200. then we gave 180v. how many rpm of its motor. gave answer with calculation at my ID.... ravizak@ymail.com
What is MSL designation of a motor and same may be provided in details.
why the value of k is more in shell typr transformers?