When a field input to plc is coming from 400 to 600 meters
and the input is in 24 V DC? So signal cable of which cross
section i should select for proper signal to plc?
Answer Posted / laxit
For this type of circuit, use Relay output instead of
direct driving through the PLC output. As these SOV's are
not the low power wattage, Prefer to use 2.5 Sq.mm as a
general for such digital output.Relay contact shall be
selected accordingly.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Explain the use of hair spring in the pressure gauge.
What is loop1 and loop2 in MTS LT?
I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.
i am from instrument branch i want paper patern of mahagenco . any pevious years paper regarding my branch send me please . please.....
Gas equation
what would be the minimum flow rate that we can measure on rotameter..?
draw the block diagram of a level transmitter ?
Hi Friends i need Electronics&Instrumentation Engg question papers for BARC written test by coming 20th May 2008 pls post ur use full info to kkumarei@gmail.com. Or for suggestions pls give one missed call to 9962122264
Specific gravity.
plz you help about Que paper of mahagenco previous your,any model paper relad to it{maharastra power genration}
Which topics are covered in Process Control?
Why mixer nd grinder Is example of constant torque load not variable torque load ???
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
What is voltage regulator?
how is work pressure switch& level switch?what is the principle of this?