Why is it that bus reactors are not accompanied by a neutral
grounding reactor whereas a line shunt reactor is? PGCIL
does so.
Answer Posted / subbarayalu
In EHV Line, if there is single pole auto reclose used, during single phase fault, the faulty line may have arc current due to resonance which will disturb the auto reclose. Also, there will be transient recovery voltage. To compensate this effect we require Neutral Reactor in the EHV line. Whereas the same Auto Reclose condition will not be in Bus Reactor breaker. Hence, neutral grounding reactor is not required in Bus Reactor
| Is This Answer Correct ? | 16 Yes | 3 No |
Post New Answer View All Answers
Can anyone provide with a SLD for HT panel installation for a 33KV line and distribution end has three 1.5MV transformers. Is it suitable to use OCB or VCB and also provide me the suitable rating and its connection diagram.
how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?
How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?
Sir, I m 3rd year student 4m DCE and want to do internship in siemens or l&t or any other mnc related to electrical engineering. please tell me the procedure 4 same and oblige me
please send the IS strandard for electrical to sakthi_murugan86@yahoo.co.in
what is zinc diffusion?
how open delta PT works & what is its construction?
What do you mean by Stimulastion Test in Diesel Genarator / Why & when it's conducted ?
How to set a Zone 1 distance relay for distribution feeder?
What is safety of Ht panel
Starting times for soft starter & power factor is thier any standard or datas available in manufactures list. Kindly suggest.
When we giving the 3 phase supply to ups system how to coming netural?
explain with diagram how to protect transformers and substations from over current with help of CT's?
Why back emf used for a dc motor? Highlight its significance.
Why is remote backup preferred to local backup?