how manys ways dp transmitter can be calibrated having
range of -150 to 400mmwc,what side pressure u will apply?
Answer Posted / jigar anadkat
You Can Calibrate in Two different Ways:
1) By applying normal pressure according to the range i.e.
(-150) mmwc with vacuum pump and observe 4 mA and keeping
this pressure on LP side apply 400 mmwc in HP side and
observe 20 mA (in steps).
2) Apply 150 mmwc on LP side and observe 4 ma [HP-LP=0-150
= (-150 )], then keep LP side open 0 mmwc and create
550mmwc (400+150) span by applying pressure on HP side and
observe 20 mA (in steps). If no pressure on both the side
your TX will give o/p = 8.36 mA
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...
Speedtronic system .
What is the use of temprature compensation?
How can a d.p. Transmitter be calibrated?
how many types of viberation transmitter and how to calibrate and where use of vibration transmitter
why using negative supply for bentley nevada vibration system ?
how can i calibrate the temperatuture gauge used by temperature bath(dry block) i mean step by step procedure?
what is gas metering system? gas chromatograph? and gas compressors?
hello friends, can you please send me the model paper or question paper to be prepared for hpcl examinations????????? You can mail me at rahim_here@yahoo.com waiting for your reply........... help me .. plz.....
How does a single acting, spring return ball valve actually work? Does it require continuous air supply?
in mass flow meter what is drive friquancy ?
3. Differentiate between ultrasonic flowmeter and radar type flow meter.
how to control pid
What is eddy current? Describe the operating principle of proximity probe.