What is Vk and Imag i.e Knee point voltage & Magnetising
Current?
How to calculate above values?
How to define accuracy class 5P10?
Answer Posted / ugrasen
Dear friend,
Knee Point voltage is nothing but a point at which the CT
saturates. Thatsy its always better to design the CTs which
can operate without saturation even at a voltage appears in
the CT during fault condition. Pls find below the following
formula for calculating the Knee point voltage.
The formula for Knee Point Voltage is:
Vkp = K * If/CTR * (RCT + RL + RR)
in which,
K = Constant, conventionally taken as 2.0
Vkp = The minimum Knee Point Voltage
If = Maximum Fault Current at the location, in Amperes
CTR = CT Ratio
RCT = CT Secondary Winding Resistnace, in Ohms
RL = 2-way Lead Resistance, in Ohms
RR = Relay Burden, in Ohms
ugrasen.vishawakrma@gmail.com
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
Can RCD's used to protect the VVVF drive if not why.
What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?
working function importance of mdc meter
In radial network the source is fed from 1 end both ends at central
Is there any type of starter for DC motor other than two point,Three point and Four point starters?
Discuss the effect of sudden loading of an induction motor
How many types of electrical earthing are there?
what will happen if the prime mover on the field excitation of the on-coming generator fails?Explain.
The size and construction of bushings in a transformer depend upon?
What is the ratio of true power to apparent power in an ac circuit?
How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?
Which test will be more severe for VCB?
what are the stresses in circuit breakers ?
A car's starter motor draws a current of 100 A at 12,0 V when starting the engine. The mechanical power required to turn the engine is 960 W. At what rate is energy from the battery converted to non-mechanical forms of energy?
what are the differant std sizes of cable trenches?