how to calculate short ckt current of trafo.
ex.3-ph 3MVA trfo. 11/440, impdence voltage=7.25%
Answer Posted / annonymous
Fault MVA = 3MVA/0.0725= 41.38MVA
So fault current on 11kV side= 41.38/(1.732x11x0.8)= 2.715kA
fault current on 0.440kV side=41.38/(1.732x.44x0.8)= 67.87kA
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
how can we save enegry by using VFD for Resiprocating Air compressor which is having more unloading running hours
Draw the wave shape of armature current in a generator subjected to a sudden three phase short- circuit at its terminals. Define various reactance of generator from this wave shape.
i want bhel placement paper for electrical if anybody having pl send to my id kavitha867@myway.com immediately
what is the step by step formula for calculating bus bar phase and neutral size of a panel board.suppose the incomer of panel board is 100A..???step by step answer please
WHAT HAPPENED DC SERIES MOTOR FIELD WINDING OPEN. CAN POSSIBLE.
Mention the disadvantages of low power factor? How can it be improved?
What happens if the series current double?
What consists of 2 or more thermocouples to be connented series?
What is an order of a system.
Why the moulded plug comes with domestic appliances instead of assembled plug like anchor, Vinay 5/15 A.
What is Scheme Test of High Voltage Switchgear. Which tests it includes.
Name two types of electrical analogous for mechanical system.
what are the basic insulation levels & what its Unit
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
what is mean by kneepoint voltage? when it will happen? ( my doubt is, if CT secondary is open means ct get saturation or blas? what are factors are required for calculations? plz give currect anws: