How do we calculate the weight of aggregates, sand and
cement M 25 design mixfor 1 cum
Answer Posted / sjtbehera
. REQUIREMENTS
a) Specified minimum strength = 20 N/Sq mm
b) Durability requirements
i) Exposure Moderate
ii) Minimum Cement Content = 300 Kgs/cum
c) Cement
(Refer Table No. 5 of IS:456-2000)
i) Make Chetak (Birla)
ii) Type OPC
iii) Grade 43
d) Workability
i) compacting factor = 0.7
e) Degree of quality control Good
2. TEST DATA FOR MATERIALS SUPPLIED
a) CEMENT
i) Specific gravity = 3.05
ii) Avg. comp. strength 7 days = 46.5 more than 33.0 OK
28 days = 55.0 more than 43.0 OK
b) COARSE AGGREGATE
i) 20mm Graded
Type Crushed stone aggregate
Specific gravity = 2.68
Water absorption = 1.46
Free (surface) moisture = 0
c) FINE AGGREGATE (Coarse sand)
i) Type Natural (Ghaggar)
Specific gravity = 2.6
Water absorption = 0.5
Free (surface) moisture = 1.4
3. TARGET MEAN STRENGTH (TMS)
a) Statistical constant K = 1.65
b) Standard deviation S = 4.6
Thus, TMS = 27.59 N/Sqmm
4. SELECTION OF W/C RATIO
a) As required for TMS = 0.5
b) As required for ‘Moderate’ Exposure = 0.55
Assume W/c ratio of 0.5
5. DETERMINATION OF WATER & SAND CONTENT
For W/C = 0.6
C.F. = 0.8
Max. Agg. Size of 20 mm
a) Water content = 186 Kg/cum
b) Sand as percentage of total aggregate by absolute
volume = 35 %
Thus,
Net water content = 180.42 Kg/cum
Net sand percentage = 33 %
6. DETERMINATION OF CEMENT CONTENT
W/c ratio = 0.5
Water content = 180.42 Kg/cum
Thus, Cement content = 360.84 Kg/cum Adequate for moderate
exposure Say 360 Kg/cum
7. DETERMINATION OF COARSE AND FINE AGGREGATE CONTENT
Assume entrapped air as 2 %
Thus,
0.98 cum = [180.42+360/3.05 + {1/0.33}*{fa/2.6}]/1000
& 0.98 cum = [180.42+360/3.05 + {1/0.67}*{Ca/2.68}]/1000
Hence,
fa = 584 Kg/cum
Ca = 1223.8 Kg/cum
The final mix proportions of M-20 grade of concrete become:-
Note: 1 The above recommended mix design must be verified,
by actual cube tests.
2 The mix design is based on the quality and grading of
the materials actually supplied, by the client.
Any variation in quality and gradation will result in
changes in the mix design
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
why does the most of civil engg is not intersted to going for teaching field?
What is the requirement for over all CG of DG from the foundation surface to absorb the vibration of heavy set.
How much percentage of brick bats allowed in CD-75 bricks
What is the usage of zoom command?
Types of column foundation and how to calculate its steel quantity.
What is modular elasticity?
what is pile and deam foundation
in block masonry l=10',b=0.5',H=10',Calculate cement ,sand and no.Of blocks?
design the irrigation canal(b,B,h )head is 3tms of water is supplied to the 200hectars of area and the base period crop is 150days dance to water travels as 35km.the canal section is trapezoidal and also calculate the slop the canal
What are the different theories of failure under static load?
Journal entry Gross salary 10000 Tax 1000 Employee contribution 2000 Employer contribution 2000
what is the meaning of 40/20 src
In the roof of a pumping station explain briefly the components of a waterproofing system?
How much wastages taken in 1. cement 2. steel 3. fine aggregate 4. coarse aggregates (10mm, 20 mm)
what could be the production cost of 1 cum of concrete by CP30 plant