Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

hw to calibration a control valve?

Answer Posted / sajid ali khan

In addition to the Calibration, it is also crucial that the
Control Valve (CV) response matches the demands of the
controller.
Normally, the CV is calibrated and checked as already
mentioned in this post, but please appreciate that in real
operation, for most of the time the controller output will
change in very minor amount to counteract the process
upsets or set point changes and the CV need to respond
rapidly and effectively to those changes. Thus if you
observe any CV, or note its trend from the Control System,
you will see movements in fractions of mA/psi etc. Very few
CVs will go to the full close position and valve going to
the full open position is even rarer.
Also, it is necessary that the CV overcomes any stiction,
has minimum hysteresis as well as little dead band.
Therefore, it is important the valve be checked for minor
changes.
How to check that:
1. Move the valve to any position other than at its
extremes, somewhere in the middle.
2. Find a safe spot on the CV stem where you can feel the
minor CV movement against a fixed part of the CV Body. Put
your finger firmly on that spot of the CV Stem. I
repeat “SAFE SPOT,” otherwise if the CV operates suddenly
your finger may be injured.
3. If the CV has a digital positioned with a feedback, the
observation may be simpler and finger feeling may even be
not necessary at all.
4. Now closely observe the CV input signal, preferably the
pneumatic signal on a 6 inch dia pressure gauge of at least
0.5 % accuracy. If digital pressure indicator of similar or
better accuracy is used that would be better.
5. While applying input signal move the CV a small amount,
then apply reverse signal very gently and slowly, and feel
the CV stem movement with your finger, the stem should
move. The numerical value of the input signal against the
minor can be noted from the factory test data of the valve.
In case that is not available it would be known by
experience.
6. Repeat this exercise at two or different CV openings and
always check in forward and reverse directions, till you
are confident of the CV performance.
7. In case valve sticks, shows excessive dead band etc,
then loosening of the stem packing or even CV opening for
inspection to check stem/plug misalignment, or hardened
stem packing may be the culprit.
Regards,
Sajid Ali Khan
engineersajid52@gmail.com

Is This Answer Correct ?    7 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is The specifications for oriface instalation

2198


what is a half wave, full wave, and bridge rectifer.

1836


What is hp & mp seperator .& what is its working principle ?

2687


How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?

5962


How does a single acting, spring return ball valve actually work? Does it require continuous air supply? 

2192


I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.

1947


How many ohms are required for proper earthing?

1130


In control valve proximity inductive sensor is taken as digital feedback for full open and full close.Normally its volts 24v when the sensor acts the feed back voltage 14v so that our relay not indicating in plc panel . kindly give the solution.

2019


send me HPCL paper

10484


How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?

2081


how to calibrate 0- 150 psi presure gauge by dead weght tester

2111


Tell me the field calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter.

3255


what deference between panel earth and systemearth

2378


Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows

2144


I WANT SECURITY PAPER MILL, HOSHANGABAD TEST PAPER.KINDLY SEND TO MY MAIL ID

2827