What is the suitable rating of MCB for 1.5 Ton A.C and why?
1Ton= how many amperes?
Answer Posted / vishvajeet
Because of compressor at the start current may be more than
5In , but once atrted it will take In only , os 'C' type
mcb only should be refer , now current depends upon the
watt rating so uo to 2.5kw 16 amp MCB can be used but if it
is more than 2.5 kw to 3.5 kw go with 20amp mcb only
Is This Answer Correct ? | 34 Yes | 13 No |
Post New Answer View All Answers
Is the theorem applicable to ac sources?
EXPLAIN THE TRANSFORMER MAINTENANCE?
details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?
which is better to use svc or synchronous condenser why ?
When semiconductor fuse does save thyristor in each cycle of conduction? Why under voltage setting keep less in SPRS and more in DC drive?
how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?
difference between crane drive and line drive.
how to do the ductor test?
What is MS-EXCELL?
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
which type of motor is used in automatic swing gate
Has someone here done a sizing for a generator (3 phase), its for a pumping station. If you have an example for standby/duty and both running (I) star delta (ii) Soft Starter.
draw the restricted earth fault protection circuit install on power transformer and identify its parameters and draw C/C curve of it
WHAT KIND OF LIGHTENING PROTECTION SCHEMS CAN BE ADOPTED FOR THE FLAT ROOF OF BIG DIMENSION.
why the name trunking bus PT