HOW TO CALCULATE THE CAPACITOR RANGE FOR LOAD FOR PF
IMPROVEMENT?
EXPLE:FOR 65 HP LOAD HOW TO CALCULATE CAPACITOR RANGE?
Answer Posted / manish deswal
let us conside current p.f = .8 & improved to .9,
Load = 65 hp =65 * 746 = 48.49 KW
KVA1 = 48.49/.8= 60.61
KVAR = Squareroot of [ square(60.61)-square(48.49)]=36.36
KVA2 = 48.49/.9= 53.88
KVAR = Squareroot of [ square(53.88)-square(48.49)]=23.49
Increased Capacitor bank capacity = 36.36-23.49 = 12.87 KVAR
| Is This Answer Correct ? | 3 Yes | 3 No |
Post New Answer View All Answers
salam,hi, i need to know what the spesification of 300amp msb...
how many joints are allowed in underground HT cable of 1 KM
Define end float in a motor?
c++ write a program to use a fuction call "max"which accepts an intger arrey of size5.as an arrument and return the larger and smallest of the arrey to main without changing. the original changing of the original position of the element of the arrey.
What are the weight of 800KV DA,DB and DC type tower ?
Draw the vector diagram and condition for the following: 1) Dyn1 2) Ynd0 3) YnYn0
WHY IS THE EARTH FAULT CURRENT ALWAYS LESS THAN THE NORMAL CURRENT??
what does a string of resistors in a series will do?
power transmission pole used one support , that only for support or earthing
what is feeder bay?
what is meant by motor startup supervision & motor load jam protection ?
in my working site. momentary jerck in electrical supply ocurred frequently which cause of multiple losses in our electrical equipements. how can we protect our electrical machines and equipements in this situation.
how to calculate the settings for shaft ct protn in hydro generators
Pl.brief me about Electrical power distribution system from Main generating station to Industry.What is the use of in between station.
How will polarity test of Dy5 Transformer ?