Answer Posted / satish
This type of protection provides a continuous check on faults within the points, where the C.T.s are used as in shown in fig 2. There are two sets of C.T.s; each set is mounted on either end of the stator phase. The secondaries of these current transformer sets are connected in star and their ends are connected together through pilot wires. The over current inverse time relay is connected across the equipotential points in the pilot wires, which will naturally be in center of these wires as shown in fig 2. But it’s convenient to locate these relays adjacent to the main circuit breaker; this can be achieved by inserting balancing resistance in series with the pilot wires to achieve equipotential point near the main circuit breaker as shown in fig 3. If there is no fault in the generator, same current will pass through the C.T.s at both the ends and there will be no current spilling into the relay.
Now if earth fault occurs as shown in fig 2, there will be an increase in current through set C.T.1 as compared to current through C.T.2. Thus there is no current balance any more resulting into spilling of current through the relay R hence tripping the circuit. If there is short circuit between the two phases as in fig3 it will also cause operation of relay R and tripping of the circuit breaker. This scheme does not provide protection for the turns of same phase
| Is This Answer Correct ? | 13 Yes | 3 No |
Post New Answer View All Answers
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
what is meant by tranformer impedance?
How LT megger works ?
EXPLAIN THE ESSENTIAL FACTORS WHICH INFLUENCES THE CHOICE OF SITE FOR A HYDRO ELECTRIC POWER PLANT
what happen when we add mentos in cold drink?& why?
our industries ht line so power fluctation(once drop of power please rectify causes
what is meant by rotating magnetic filed
Diagram on interconnectivity of 11kv transformer with RMU (i.e, one incoming and two outgoing or two incoming and one outgoing)
types of central Air conditioner plant?
what is the effect of un-synchronized power.
Formulae for calculating the transmission line losses for different voltage levels
what is counter poise conductors
what is the use of piston rings in the engine used for a generator...........
5- What is the task (function) of the excitation and isolation transformers in power plant? 6- What is the task (function) of LCI (A), LCI (B) and LCI (COS) in power plant? : LCI (A) and LCI(B) are load commutating inverter for generator turbine starting. , LCI (COS) is load commutating inverter change over switch