I work on a electronic positioner transmitter 4211 at the
field.I connect my multimeter in series to get the current
output then I calibrate it to 4ma in 0% of position of the
valve and 20ma in 100% position of the valve.My problem is
in the field I get the correct output current based on my
multimeter but in the dcs they only receive 40% in a output
20ma of this positioner.Then I try to simulate in this
analog card and they receive the equivalent percent on the
value that I simulated.Is ther any possibility to reset the
zero and span of this positioner 4211 fisher.And what other
possibility I can do to fixed this.This is my email add (
landicho_randy@yahoo.com )
Answer Posted / randy landicho
AI card is two wire and the electronic positioner
transmitter is also two wire. I already simulate ma directly
into the card and the DCS receive the equal percentage of
the ma that I simulated.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
what is the different between deflection type measurement and null type measurement in RTD?
Explain the burnout feature.
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
Explain bernoulli’s theorem.
How is work 5/2 sov?
sir, i preparing hpcl,ongc,barc,hal exams(instrumentation engg)pls send a placement papers
how to relay switch sense the fault?
What is the GK Value in Flowmeter?
What are different types of valves?
May I have a brief note above the voltage barriers? Whats is the purpose? Please mail me if you've operational details, mail id: rajkumar.diice@gmail.com
what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?
what is the difference between profibus and controlnet networking.
what can of fault ofently come in vibration mesurement?
In turbine, what does term CDP, NI, NH, HSSOC, means
line up procedure for dp type flow transmitter?