Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to check thermocouple ,its working or not?

Answer Posted / senthilnathan.j vizhidiyur

If you are going to test k-type thermocouple at normal room
temp.first you check the resistence of the themocouple using
multimeter.if junction is open then it shows Mohms means the
thermocouple is dead.it will show 0 resistence when it is in
good condition. then you check the milllivolt output by
touching the terminals with correct polarity (For k-type
red-positive; green-negative) using multimeter.at room
temprature the output of thermocouple is 0mV because both
the hot junction and cold junction are in same temprature
say 30deC.
then set the hotbath temp. into 100C and put the T/C inthat
and now check the T/C teminals it should show 4mV because
for K-type For 1degC =0.04mV will rise.It is difficult to
find that much minimum voltage.so that only we are taken the
reading at 100degC. now you are successfully tested the
Thermocouple.

Is This Answer Correct ?    8 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?

1620


Explain the combusion chamber

2030


Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.

1935


why is an oxygen sensor used in a boiler stack

7324


what are the diff. in servo and regulatory control?

3979


sir ,iam in dem urgent need of HPCL Paper of Instrumentation Branch plz send me at your earliest convenience at ujjwal_sharma1983@yahoo.com

2518


what is the process for double acting cylinder pneumatic for 32' v/v

2078


How is work 5/2 sov?

1889


I have energy meter for educational project having 0.5s class but my friend need 0.2s class meter , which one is good for that purpose and what is the actual difference of that two classes , need very easy example also.??

1406


what are the definitions of input, output, command & signal according to instruments controlled by PLC using DCS System?

2126


Hi, I am Newely Joined in Construction company instrument engineer? Any one can Plz tell me How can I advanced preparation for Releated Engineering and construction Documents?

2564


How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?

5914


what diffrence b/w plc s7200,300,400

2073


Why ac supply load cell is used? Can we use the dc supply load cell?

1070


please tell no. & add. of consultancy who recruit me in power plant as instrumen engg. present i m working in power plant as ass.t instrument engg. thanku mahesh 09226562826

2091