Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

725KW Three DG set Synchronised but DG no-1 power showing
750KW DG n0-2 power showing 500KW DG no-03 showing 500KW.
DG is Shynchronised but why this different power showing?

Answer Posted / jince

Regarding paralleling DG sets we sticks only on the theoratical conditions of same voltage frequency phase angle and phase sequence. And now a days its easy to achieve using sync relays. Load sharing is the major thing in paralleling the DG sets. Many factors are depending on it
1. Droop of individual DG set must be same
Droop implies both voltage and frequency droop. it is the percentage of noload voltage or frequency. ex. 1% 2% 3% etc. Ex.1% voltage droop of 420V(noload)is 4.2V and it means on full load DG voltage comes down to 415.8V and not any more
Same is the case with frequency droop. All DG's droop must be same

2. On loadsharing we adjust voltage of DG's to met REACTIVE POWER AND SPEED(FREQUENCY) TO SHARE ACTIVE POWER

In order to share the load evenly we must control the voltage and frequency of individual DG's constantly

And it depends on load nature
In my personal experience for resistive loads (lamps)
loadsharing is not required as no variation occurs

For varying loads like lifts motors ac chillers compressssors etc constant loiadsharing is required


For clarification please reply

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A low wet bulb temperature indicates

1207


what is the calculation involved to design the heater to heat 10KL of water in temperature control unit?

2005


which pump used in STP

2282


what is the ckt diagram of a tubelight and is it the simplest ckt of electrical engineering and also the component?

2436


What's the difference between non break power supply and non break non short break power supply

1509


The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?

1761


Why derating factor os applied on Cables?

2006


if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm

2325


If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..

2553


what is the differences between microprocessor and general purpose computer

2239


how to select battery for 15 KVA UPS with formula

2595


How DC earth leakage currents can be reduced ?

1967


I have finish diploma electronics and five years experience in electrical field in ht service how can i get c licensce or other electrical certificate

1742


What is meant by Im=30mA@Vk/2. How to know the kee point voltage for CT design

3515


Can we use shunt trip coil instead of trip coil with protection relay for protection?

1781