How to check vortex flow meter is in good condition while
we do not having calibration setup?
Answer Posted / krishna reddy
Let me know first which make you have.
Instrument have min and max ranges on its name plate.
So wiht multimeter you can check 4-20ma of flow meter.It
must be 4 ma if flow is zero and 20ma if flow is max range.
supose your flow mete got 100L/hr.
for 4ma flow should be 0 L/hr
8ma - 25L/hr
12ma - 50L/hr
16ma - 75L/hr
20ma - 100L/hr
Like this you can check.
| Is This Answer Correct ? | 10 Yes | 3 No |
Post New Answer View All Answers
What are the types of control valves available
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
what are the diff. in servo and regulatory control?
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
please someone tell me what is function of vibration sencer and how many types and how to control viberation.please. my id is jimmykhan077@gmail.com
How the sizing of the analog signal cable is calculate?
Why flow/pressure transmitter before control valve?
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
What is Erosion in a control valve?
for oil & gas industries which zone is normally preferred? why? give its example?
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
In apron feeder how TPH is calculated?
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?
Q-Explain the different load conditions that will produced different offset which may or may not be acceptable to thhe control function