To measure insulation resistance of 11KV cable between core
& armour, what should be the test voltage & duration?
Answer Posted / sujeet pandey
To measure the insulation resistance of 11kv cable, we need
to keep Megger test voltage at 1kv and take 2 readings; one
at a interval of 15 sec and other at an interval of 1 min.
This will give Absorption Factor which is equal to ratio of
resistance at 1 min to the resistance at 15 sec. If the A.F.
is less than 1.2(a/c to Indian Standards) then the
insulation is not good and we must take the remedy action.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
what is meant by k-rating in isolation transformer?what is k9, k14 stands for?
what is buffer resistance starter.?.What is the working principle and where it is used..?
how to decide the panel size like MDB ,SMDB PANEL SIZES
difference between power surge and switching transient
Hi, Next week Iam appearing RRB exam for section engineer. So help me to get modal question papers for this position. Iam very thankful to you. Whether question will be fully techanical format or general form. Please give me a details regarding this exam.
At the starting of dc motor and syn.motor and induction motor high current flowing through the winding. Due to this the windings burnt out. To avoid this different types of starters are used. But incase of transformer what Will be used (At starting no emf is induced in the primary winding)?
How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?
What is vaccum currcuit breaker.define with cause and where be use it device?
How many types of losses occur in a transformer?
what is the difference between electrical and electronic choke?
Why is water motor not taking the pressure? what is the problem?
What do you mean by lighting transformer?
why effective resistance should be more than static resistance in transmission line?
Load transfer in 11kv double busbar switchgear - operation.
if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer