Why capacitor bank does not require in DG Set?
Answer Posted / kishor kajrolkar
It is possible to switch on high speed microprocessor
based capacitor bank on running d g set.But with A P F C
ie. contactor based can be used with time delay So as it
will result in zero voltage available on terminal of the
capacitor.( during switching of said capacitor bank on
running generator).However one must think of no load
condition of the d g set so as to use sensitive steps for
capacitor in the circuit.It is observed most of the load
in IT sector having non linear loads ,hence result in
impure power as well as low powerfactor leads to additional
loads.Capacitor used to filter harmonic current and change
of the power factor need to classified before application
the bank.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Discuss the effect of sudden loading of an induction motor
i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester
how to calculate earth fault relay current and CBCT ratio
is IS says that neutral should be brought to switch box. and this one is a recomended practice
harmonics filter
Mention the difference between Analogue and Digital circuit?
how choose conductor&depending upon load
What will be result if we connect LT votage to the terminal of HT motor?
describe the A.C. Generator Testing procedure
how is calculated the quantity of weight in hot test xlpe?
plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in
Define de-sensitivity?
define displacement & magnitude ?
DG SET BLOCK DIGRAM
why the earth is taken minimum in supplying? wather it the proportional factor to getting work any equipment or a power plant?