Answer Posted / antaratara ghosh
assuming the load as motor,operating voltage as 415 V,pf
as .85, efficiency as .95,
rated current, Ir= (644)/(1.732*0.415*0.85*0.95)
= 1110 A (approx)
now considering VFD starting for the motor,
starting current, Ist= 2*Ir
= 2220 A
considering margin of 20%, maximum current flowing =
2220*1.2 = 2664 A
Since MCCB are not used above 630 A in India, you have to
go for 3150 A (which is just greater than 2664 A and
available in market) ACB...
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.
What are the advantages and disadvantages of the ac motors?
Which thing is maximum in RLC circuit at resonance a)power consumption b)inductive current c)capacitive voltage
whether starting current is limited to rated current of motor through soft starting or it exceeds the rated current?
What is meant by sag?
why not starting switch first connect in direct on line starter?????
What are the limitations of Kirchoff's laws?
what is meant by power and distribution transformer ?
is that any software calculator to calculate the size of cable
Phase control and integral control are used for?
What are the internal and external faults?
State any two nuclear power stations in India, with their generating capacity.
What is the safety of UPS?
A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?
where is the need for short circuit test for 3 see is required and why? can you explain in brief with application