WE HAVE A LOAD OF 55KW MOTOR ITS VOLTS 380 3PH AND ITS
TAKING 100AMPS (ITS FULL LOAD IS 105AMPS)AND ITS CABLE IS
4CX50SQMM ,NOW ITS GETTING ABNORMAL HEATUP IN CABLE,PLZ
TELL WHY ITS HEAT-UP?(CABLE LENGTH IS 15 METERS ONLY)
Answer Posted / manohar
If motor is connected in Y/D connection, then the cable size
is used OK, Check the both motor & panel side terminal
connection is loose . After this if you found cable heating
then check the voltage,current& POWER FACTOR. If necessary
put 25KVAR Capacitor Bank at motor side.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
H.t motor 6600 volt to same motor lt supply 440volt supply applyed to h.t motor to effect....
How does a television work?
being an electrical engineer why you wanna come into software i have an very good academics what answer i have to give
difine electrical ballast in HPSVL
what is the difference between c power and U power acb breaker
Pl.brief me any electrical major fault you have rectified.
What determines the thickness of the lamination or stamping?
WHY DO VOLTAGE TRANSFORMERS FAIL DURING EARTH FAULT IN THE DELTA CONNECTED 6.6KV ELECTRICAL SYSTEM
What are the electrical engineer roles and responsibilities in chemical plant?
I WANT HOW CALCULATE TO CABLE FOR WELDING PLANT ?
Define phase cross over?
A 100KVA SINGLE PHASE TRANSFORMER 10000/200V,50HZ REQUIRES 300V AT HV SIDE TO CIRCULATE FULL LOAD CURRENT WITH LV SHORT CIRCUITED.THE INTAKE IS 1000W.THE % OF REGULATION ON FULL LOAD AT 0.8 PF LAGGING WILL BE HOW MUCH AND THE SECONDARY TERMINAL VOLTAGE ON 0.8 PF LEADING WILL BE
what is excitation/
What are test signals and their significance?
how to decide the panel size like MDB ,SMDB PANEL SIZES