our company have 750 kva oil transformer.still we have
facing a problem that is when voltage is 11.5 kv coming
from HT side then LT-side voltage is 420v or above at tape
1.please give me best solution to decrease the voltage
Answer Posted / sudhakar lanka
my friend, you r looking for reduce the output voltage from 420 volts,
case1: try to keep the primary tap position on maximum voltage
for example ur receiving 11.5kv , if in your transformer there is a tap voltage which is more than these value i.e 11.6kv or else apply 11.5kv on that tap position.
same as above u can try on secondary side also
case2: if u have done all the these exercise, then when u connected to load on transformer there will be voltage drop
check at that time may be ur required voltage i.e rated voltage on motor or machine when it is running on load
other wise u can check with grid supply or substation to get required voltage
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?
What are the reasons for the parallel operation of transformers?
why three phase capacitor takes unbalanced current in capacitor bank?
why the carbon brushes are broken in srim while the motor runningtime
hi guys please tell me the procedure for mesuring the coil resistance of 3ph induction motor?
I'm looking for a mnaual set for a Teradyne J750. Softcopy would be preferred but I'll take what I can get.
What is the importance of counter based plan & how is it scheduled?
what is the setting of locked rotor in HT motor ? (answer expecting in percentage)
if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?
solar inverters was not connected to the nuteral link .this nutwral possible to any other systems
Whats the difference btwn a latch, port,data bus buffer? Do they all not hold data in d flip flops??
why do we use 25kv supply for traction purpose?
I need the recommended size for a 3 phase transformer at 13.8 KV Primary and connected loads of 3000 kVA at 4200 volts and 2375 kVA @ 480 volts AC.
how do prepare ongc exam.how is it question model.i am electrical. which part covering in electrical.tell me
why single phase to grd test in HV cable?why not 2 phase at a time?