in our 6.6kv motor feeder[it is having two sources from
Bus A&B] earth fault relay is acting, we checked CBCT
connection and cable meggerd values found very good still
earth fault acting during first two are three start after
that it will hold. please clarify what was the reason. if
same motor is starting from other Bus-A it will start.

Answer Posted / a.p.nanjappa

WHAT IS THE TYPE OF 6.6KV SW.GR. hOW OLD IS THIS?
tHE EARTH FAULT RELAYS ARE VERY SENSITIVE. INSULATION
RESISTANCE OR MEGGER CAN NOT MEASURE.
CARRY OUT HV CAPACITANCE MEASUREMENT OF MOTOR,CABLE FEEDER.
AND hIGH POT TEST.
MEASURE THE TANGENT DELTA FROM DC HIGH POT.

IF MIN OIL CIRCUIT BREAKER,TEST THE OIL AND REPLACE.

WE ALSO EXPERIENCED THIS DUE TO BURNED CEREMIC/BAKELITE
PARTITION PLATES OF 6.6KV SW.GR

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is Surge Capacitor? Why it is use in Generator Circuit Breaker?

4609


how does an encoder work???

2044


what is the setting of locked rotor in HT motor ? (answer expecting in percentage)

1801


What is the size of a 60 watt and 80 watt tubelight?

1755


DEAR SIR,I GOT THE CALL LETTER FROM RRB, SECUNDERABD AS A JE-II SO PLEASE PROVIDE ME SOME MODEL QUESTION AND ANSWER PAPERS AND LAST YEAR QUESTION PAPERS

1623






what is the difference between droop mode and ischnorous mode in thermal powerplant?

2169


there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit

1495


While performing stability test of differintial cts how to know the voltage and current on both side of the transformer?

3068


where is the need for short circuit test for 3 see is required and why? can you explain in brief with application

1413


Hi Everyone ! My Name is Hakim ullah khan please i need formula of Cable Rating because i want to calculate by self without check any Table Chart... Thank you.....

1253


Is there any reason that we get shock on touching phase wire because the earth is at neutral potential? Is there any reason that the earth is at neutral potential because the neutral is earthed in apower station

1556


What do you mean by lighting transformer?

623


whats the application of voltage regulation? and whats the voltage regulation's device?

1416


State the formula for overall efficiency of thermal power station

2549


What does the term “voltage regulation” means?

633