What is the basic difference between 90% stator earth fault
and 100% stator earth fault, and its phenmenona?
Answer Posted / a.p.nanjappa
This is an application with power plant genrator protection.
In early 1950-75,only 90% stator earth fault protection
used for Generator Stator winding.
GE,westinghouse,hitahachi,GEC,BBC,KWU.ON 1975 ONWARDS,
THEN 100% STATOR EARTH FAULT DEVELOPED USING OPEN DELTA
VOLTAGE OFGENERATOR AND USING FIRST AND THIRD HARMONIC
BRIDGE.
WEST AND EUROPE,INDIA USED GENERATOR NETRAL GROUNDING
TRANSFORMER AND ON SECONDARY OF THIS TRANSFORMER90%STATOR
EARTH FAULT PROTECTION IS USED.
FOR 100% STATOR EARTF FAULT USE OPEN DELTA VOLTAGE.
Russian practice is use voltage transformer for generator
neutral gounding.
when I was DISCUSSING this with european manufacturer, they
want to delete 100% protection.In a generator it is meaning
less.fault is fault.It is time consuming for repair.
As a new challenge-generator manufacture claim 100%
availabilty of Generator with VIP.
/MICADOUR ELASTIC INSULATION. In gas turbine a single
generator rating is selected for single shaft gas turbine
and steam turbine. upto 275MW. AND 400MW
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
how to calculate the tarriff for an industry whose kva demand is 10 mva
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
-How do you select cable size for a given load at a given distance from source of supply. How do you find voltage drop.
what is basic difference betmeen normal & flame proof motor??
from which subjects most of the technical que will b asked for hpcl(electrical).pls help me
what reactive how to maintain
How to calculate multiplying factor of dc energy meter
why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?
When we need up only in o/p 440v, so why we use directly in 11kva in input?
how much allowable resistance that can be difference in motor all coils?
What are dependent sources?
what is the difference between the voltage of 5 volts capacitor and and 5volts battery?
what is meant by the phrase 'static load' in case of shorting in a generator excitation system?
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1
DEAR SIR,I GOT THE CALL LETTER FROM RRB, SECUNDERABD AS A JE-II SO PLEASE PROVIDE ME SOME MODEL QUESTION AND ANSWER PAPERS AND LAST YEAR QUESTION PAPERS