Will it be OK to connect a 5MVA 33/6.6kV Ynd11 Transformer
to a Star connected Motor. Or on other words connecting a
Delta to a Star.
I have another 30MVA 33/11 Dyn11 and would it be practical
to convert it to Dd0 consequently converting the Voltage
Ratio to 33/6.35kV Dd0.
Answer Posted / a.p.nanjappa
yes. what is the capacity of motor?
In your case , grid voltage is 33kv, Yn connected.Hence
power transformer has neutral connection brought
out.Neutral CT is installed to detect the ground faults.
secondary of 5MVA tranformer is 6.6kv,
This is Feeder bus voltage.6.6kv Feeder bus feeds Motor (
star connected). and Feeder bus is not interconnected to
another source. It is independent.This 6.6kv rotates at 30
lagging to primary3kv system.
Motor must be use inverse & instantaneous time
overcurrent and earth fault ( CDG61+cdg12) or equivalent
manufacturer protection
we use delt to star as weelas star 6.6motor.
No problems experienced.
In the othercase to change a 30MVA,33/6.35KV IS
REDESIGN/MANUFATURING. iT IS EXPENSIVE.No use at all and
advantage. You should change 6.6kv sw.gr also.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Why is remote backup preferred to local backup?
why swinburnes test cannot be performed on series machines?explain
what is motor capacity of 80TR chiller? and also say what is the formula related temperature, motor capacity, TR?
What difference between ref protection and differential protection ?
I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?
Air refrigeration cycle works on the
relation between power station capacity and voltage level?
What is the effect of pd controller on system performance?
why booster transformer is used in sumpners test conducted on transformer????
hai...... tis is Hemanth. jst now completed electrical engineering... i wanna to apper for ap tranco exam... plzz send me the previous q's paper link......thanx in advance.
what is calculation mathod/formaulla for deciding Size of busbar (Copper/ aluminum)for L.T. panel on Various Fault level like 50kA,25kA,10kA
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
What are IR values and what it should be for coil and for insulator
Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com
which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?