I am a technical persons.In one of our Electrical Sub-
Station, We have installed three numbers of
1250KVA ,11KV/0.415KV Transformer to feed the Factory load.
We have found some abnormality. In one of our Transformers
the leakeage current from transformer body to earth through
earth continuity wire is almost 86 Amp but in other
transformer it is (5-10)Amp. where the load current on
three phase and neutral are respectively
1360Amp,1400Amp,1370 Amp & 176Amp. So please any technical
person help me about the reasons of this situation and how
I can rectify the fault. Moreover,I have measured the earth
resistance of the Earth continuity wire which is less than
1 Ohm.
Thanks
Tapas Barua
Answer Posted / anadi biswas
Hi dear,
First of all tell me the condition
Are all these running parallel?If yes,then check the
individual winding to body insulation resistance with a
Multimeter.
Also you may check the transformer oil properties i.e.
dielectric strength as well in order ensure the minimum
leakages.
If individually connected , then check all the above+ the
nature of loads connected with the earthing system.
Also in all the above case check the body earthing of each
tranformer with Earth pits connected and individual earth
pits and measure the value. You will get the conclusion.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Why the symbol of register is "zig zag"
Explain and give me an example of a time when you had to explain some new procedures to your co-workers for quality service delivery, how did you go about it?
explain the function of brush less dc motor?
how to Select its CORE in electrical cables based on its applications? or Application of various types of electrical cable based on it CORE?
What is the actual calculation for transformer short circuit test?.
we have one oven for 12 zone we are installed ir lamp in oven we control load from thyrister and 0 to 5vdc so our zone no 8 getting bright in fraction of second so what we do.. Please answer
What are the types of excitation system?
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
raleigh method
What happened when voltage will half value of current ...
can some one clearly explain why -48 volt DC use in telecom site????
whate is the meaning of balance/unbalance,in stabilizers type
What happens when two positively charged material is placed together?
I COMPLITED MY B.TECH AND 10TH CLASS WITH 70%MARKS BUT 12TH CLASS 55%MARKS..CAN I GET INDIAN RAILWAY RECUREMENT EXAMINATION?
what's the difference between abs/inc encoders. apart from the position remembrance what are all the other differences. and what's mean by grey code.