Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

On a 10 KVA UPS we have to provide a DC MCB for Battery bank
of 16 nos (12 V 65 AH).
What Shall be the current rating of DC MCB ?

Answer Posted / ravi v nair

Battery banks are always connected in series so the total
voltage of the battery bank will be
12*16=192V
10KVA=10000VA
A=10000/192=52.08
we need a 55A DC MCB

Is This Answer Correct ?    7 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is servo motor and how it works?

2289


How to determine alternating current frequency?

1148


The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?

1711


3 shows a 415 V, 3-phase generator supplying a 3-phase 415/110 V transformer. Draw the individual and combined impedance diagrams to a base of 10 kVA. Determine the system fault kVA and the fault currents at the 415 V and 110 V busbars for short circuit faults on the transformer input or output terminals. Work in p.u. values of impedances.

2655


Where burned of electricity,when,who, & why.

1971


what is the terminal voltage of dc series generator running at rated speed at no load?

7608


What are the operation carried out in thermal power station?

1048


What is purpose of reactor?.What is different between line and bus reactor?

1939


what r PID controllers?why they r used?what is there purpose?plz Explain in detail

2068


Why 3 phase induction motor getting supply in body if one of it's phase is cut

1730


How to calculate multiplying factor of dc energy meter

1665


Block diagram of Power line communication?

2304


what is RNG in the DG synchronizing by PLC?

2124


what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV

2181


if we look on phasor of the transformer vaoltage is 180 oppsite at primary and the secondary so to improve a power factor is secondary should kept negative to improve it primary side means is -.90 became +.90 at other side

1854