If an Instrument has 550 ohm internal resistance and the
cable used for that instrument is 0.5 ohm per meter
resistance. If the voltage is 12volt.How much length cable
can be used? Please tell me its Calculation formula.
Answer Posted / c heman
Assume it is a 4-20 ma tx. 20ma*550= 11volts. minimum
supply is required. so allowable voltage drop is only 1
volt.
so max. 100meter u can use.
got the answer, don,t foget to say thanks.
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?
why we are not using the turbine flow meter in the steam service?
How to Calibrate Interface Level Troll in field
Q1: Consider part of a control loop, which excludes the transmitter, consisting of a process, a controller and a control valve which may be represented by two dead times of 0.5 min each and three exponential lags of 0.8 min., 1.0 min. and 1.5 min. respectively. We wish to express this system as an overall first order plus dead time (FOPLD) model ie gain, time constant and process dead time. (We will see later that this is often done, to simplify controller tuning). For this exercise, gain is considered to be 1.0. (A) If the transmitter is a flow transmitter whose behaviour can be described by a dead time of 0.2 min. and an exponential lag of 0.5 min. in terms of the overall dead time and overall first order lag how can the system behaviour be approximated ? Overall dead time = Overall time constant = (B) If the transmitter is a temperature transmitter with a temperature sensor in a protecting well whose behaviour can be described by a dead time of 0.7 min. and an exponential lag of 15 min. how can the overall system behaviour be approximated now? Overall dead time = Overall time constant =
What is Positive Calibration and Negative Calibration?
where proximity sensor installed on tank in loading arm application
What is the reason PT speed not incresed in gas turbine?
what is instrument philosophy
I am teja. I am studying Msc(tech) Electronics and Instrumentation (3years course) in Andhra university. But my course is not recognised by UGC and AICTE. Please tell me the job opportunities after this course. And i fineshed PLC course in IGIAT ,Vizag.Also complted my short term coure in SCADA, Seimans WinCC in ATI,Hyd.After Msc can i join Mtech for good job? or phd. How i can get good job in INdustrial Automation Side. Please give replay.Because this is my life matter.
use of split range ? where it is used ? in which control loop it is used ?
please send me the inteview questions in IOCL
Why we are using reverse action in displacer types level transmitters on some Vessels?
How does work A temperature valve or fv control valve in process plz brief me
protection relay watchdog contact operation?
How to control flow variations in magnetic flow maters..... When i will provide proper earthing?