In an LT pole, the line voltage is 415V. How is it
converted to 230V into the house via the service cable?
Answer Posted / kaushal
From distrubation transformer we get three phases and one
netural (due to Star connection) these four wire(three
phases and one netural)are layed over head on LT poles and
for house only one phase along with netural is used and no
convertor is used as phase to netural voltage is 230volt
between R -y- b phase voltages are 415 - 415-415 called
as line value where as between phase and neutral it will
be 415/1.732 = 239 approximately 230v called as phase value
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
What are the application of filter?
formula for calculation of switchgears(i.e. contactor, fuse, cb, relay etc.), if load current is given?
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
If 100 KAV USP dedicated earth got disconnect / Cut. What will happen at load.
2- What are the percentages between excitation currents in phase (R, S and T) in ∆ and Ỵ connections in excitation Current test in transformers?
how to i get B licence,i am completed BE electircal and electronics engineering.i want to konw the proceduure to get b licence
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
What are m circles?
Please elaborate th´evenin’s theorem?
How to synchoronize the generator (with gcb,GT) to grid????? ????? from Grid iam getting power (rated 400kv/20kv) through GT and its goes to UAT.,,ST.,, now my generator(rated 20kv ) ready.,, now iam closing my GCB.,, in GT iam suddenly giving 20kv on that Gt.,, what will happend
What is the significance of integral controller and derivative controller in a pid controller?
Difference between Lugs and Thimbles
What type of pipe material G.I or M.S is used for sprinkler system?
how to carried out DAR test in 11 KV Alternator ?
hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.