what is o2 analyzer and how it measured ,what is the role of
this analyzer in cfbc boiler...
Answer Posted / msp
:- If analyzer showing wrong on DCS than first I will
forced the analyzer value on the DCS if any tripping taken
from it.
Through the Multimeter checked the value 4 to 20 mA on DCS
or same on field As per define range in the DCS as well as
analyzer transmitter. If all things are correct than its
calibration was got disturbed. For the calibration
1 For the calibration we need sample gas and instrument air.
2 Connect the both input instrument air and sample air
through the rotameter for flow control of the both air and
sample gas.
3 Power on the analyzer and communicate hart communicator
with the analyzer.
4 For the zero calibration apply the sample gas with the
help of rotameter for flow control on the analyzer. And
press enter on the zero calibration on the hart
communicator.
5 For the span calibration apply the Instrument air with
the help of rotameter for flow control on the analyzer. And
press enter on the span calibration on the hart
communicator.
After calibration save the setting with the help of the
hart communicator.
And cross checked the same 4 to 20 mA by given the
instrument air and sample gas accordingly.
| Is This Answer Correct ? | 11 Yes | 0 No |
Post New Answer View All Answers
how to convert cubic metre per hour to newton cubic metre per hour
What are the types of control valves available
Any body have know try work calculation ???
How does a single acting, spring return ball valve actually work? Does it require continuous air supply?
What is zener diode? What is voltage regulator?
Explain the difference between mmwc and mmwg?
How can a d.p. Transmitter be calibrated?
Make a ladder diagram on LSL valve will close, on PSL valve will open and start the motor
What is stripper & spilitter ? Diffrence in this.?
What is the working principle of the magnetic meter?
HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?
What is the diffrence between ff tx and non ff tx
If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?
How can we test a bently nevda 3500/42M accelerometer monitor card by simulating it with test equipment?. what king od of signal (milli volts or volts or or resistance ) we should feed in the terminals of the card?
i want to know the interview format fot gail, instrumentation. pls answer me in habib.sami1003@gmail.com