what is air to open and air to close control valve and
difference btwn this...and how to measure milli amp by
this...and what is the role of positioner and i/p converter in
this..plz help me
Answer Posted / mohammed abdul rahman
This query is mostly related to pneumatic diaphragm actuated control valves. Air to open valves have the pneumatic input on the under-side of the diaphragm with a spring on the topside, which causes the valve to open on increase in control signal. Air to close valves will have the pneumatic input on the topside of the diaphragm with a spring on the under-side to provide counter force.
An i/p converter will convert the 4-20mA signal from control system to an equivalent 3-15psi pneumatic signal to actuate the control valve.
A positioner will have the i/p converter inbuilt and is connected to the moving part of the valve and automatically adjusts the signal to the actuator to maintain a position proportional to the signal. This introduces a loop inside a loop.
Please refer the control valve handbook from Fisher for reference. It is available as a free download.
Is This Answer Correct ? | 37 Yes | 4 No |
Post New Answer View All Answers
What are different type of instrument cable
What is solenoid valve? Where it is used?
What is the diffrence between digital signal processing and discrete signal processing?
diff between neutral ,ground,phase , earthing and shielding?
Please tell me details about Sox,Nox,SWAS analyser????
selection criteria of control valve? and selection criteria of actuator explain in brief?
How can you add value to this Industry if offered the job?
what about your moleg in pogrees with company
How to find out the current of two motors having same power consumption but different RPM?
What are de-saturators?
can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?
what is effect of specific gravity in differential level transmitter , explain formula related with this .
What is loop1 and loop2 in MTS LT?
Explain the working principle of lvdt?
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?