Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

i want to know how to calculate the battery capacity based
on the UPS . ex i want to run have one kva UPS Which should
run 10 hours ? in that case how many batteries to be
installed and what will be the AH Value .

Answer Posted / jagdish raval

UPS KVA= 1. Then KVA= VA/1000. So I=KVA*100/V. If the V=48,
Then I=21. The load of UPS is 21Amp and it have run for 10
Hours, So Battery Capacity should 210Ah.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is The Resistance Formula

1226


PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)

1913


How we select the vector group of 3phase power transformer?

2640


Can RCD's used to protect the VVVF drive if not why.

2091


how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor

3277


what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV

2127


List examples of current sources?

1064


What is an iron loss or core loss pi?

1049


Hello everyone, somebody knows what is a "surplice power" ? The hole phrase is: "This rating is appropriate for a generator set paralleled with an infinite bus e.g. a national electrical supply network or grid where the generator set is run at 100% load, 24 hours a day, 365 days a year and any surplice power is exported into the grid" Thanks in advance.

1719


which type of questions asking for solar companies?

1529


Can you explain about TEE protection scheme?

2220


How to test Alternator stability test for REF relay

1435


How is the gain affected by the introduction of feedback in a control system.

1108


What is meant by reset level of the relay?

1154


3 phase Motor will be given 2 phase after 2 to 5 second we given 3rd phase so Motor Run sum-time in forward or sum time run reverse direction. All time phase sequence is not change. Why motor run in reverse direction? Please Explain........

1903