Answer Posted / karthik ccel
If i consider your 644kW load as a motor then,
I Assumed some parameters are:
644kW Motor, Power Factor - 0.9, Efficiency - 0.9, Load
Connected Voltage - 415V Then,
I = (644*1000) / (1.732*415*0.9*0.9) = 1106Amps
Considering 20% Margin = 1106 * 1.20 = 1327Amps
Conclusion:
So, We can choose Breaker rating is higher than that
1327Amps. Generally no one use the MCCB breaker above
800Amps. So, we can prefer the 1600Amps VCB Breaker for that
644kW Load.
| Is This Answer Correct ? | 6 Yes | 3 No |
Post New Answer View All Answers
how tto ingress mw in turbine explain.procedure ?
Sir, I have applied for the of Assistant.engineer of NPDCL. please send me all AP TRANSCO AND JENCO solved papers of previous exams . I requested send me the papers to my id as soon as possible (rajanikanth_peddi@yahoo.co.in) (This is very urgent) Thank You,
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
Why can't we take NO LOAD TRIAL of motors having V1 mounting??
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
What is the function of auadag in a cro?
How to reduce -234126219.6403 MVAr generation and by what?
STATE USE OF ARC RUNNERS & SPLITTERS ?
What are the advantages and disadvantages of the ac motors?
Is electro plating what type of load whether resistive, inductive or capacitive loads
relation between power station capacity and voltage level?
how to introduce yourself
HOW TO CALCULATE AMPs OF CURRENT TRANSFORMER IN HT Panel
Which do you think is the most significant cause of energy loss in a factory?
What is reactance, reluctance,capistance, pls give answeer in hinglish and be simply Jo asani we smajh m aa jaye