how to choose the cable size for 100A(is there any formula
please update)

Answer Posted / shirish

Theory for Cable Sizing.
From Ohms law, the voltage drop in an electrical conductor is
V = I R
where
I = Current, amps
R = Resistance, Ohms

The electrical resistance can be derived from the properties of the conductor material.
R = ρ L / A
where
ρ = Resistivity, Ω mm2 /m
L = Length, m
A = Cross sectional area, mm2
Watch the units in the above equation.

The resistance can also be expressed in terms of the material conductivity (ψ) which is just the reciprocal of the resistivity.
R = L / (ψ A)

Table 1. Typical material electrical conductivity
Material Conductivity, ψ
Copper 58
Aluminium 36
Mild Steel 7.7

Combining Ohms law with the resistance expression, we get.
V = (I L) / (ψ A)

Now, we can define an acceptable voltage drop in a conductor. I have calculated the voltage drop that was used in several published tables and get around 5.5 Volts.
We could therefore re-arrange this equation to give the cable size. But cables come in standard sizes measured in mm2. In addition, you also need to consider the maximum current for each cable size.

Table 2. Conductor sizes and maximum currents
Cable Size, mm2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300
Maximum current, A 13 21 28 36 46 61 81 99 125 160 195 220 250 285 340 395
So, the theory is relatively simple, let us now see how to use the program.

Is This Answer Correct ?    0 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Differentiate between real and apparent power?

767


why should the primary of transformer be connected in delta in a heat run test?

1559


while doing high potential for 11KV 3 core cable how much leakage current will obtain?, what will be acceptance value?

2524


condition Autotrip facia come on control panel of electrical transmission line?

1185


Explain Energy and Power signals?

1399






Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1425


my name is venkat .i have good percentage in my academics(ssc 86, intermediate 83 b.tech 73) my question 1..after completion of my ssc i joined in bpc but i didnt got rank in emcet so i completed MPC in one year compartmentally ..so here what am expect question from this background?

1565


why we are using Load factor?

1446


why magnet has north and south poles only why not east and west and why we are considering as north and south poles? why cant we consider as east and west?

1605


which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?

1650


Explain the different regions in frequency response?

733


what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?

7543


what is ratio of copper wire size and current ?

1461


What is meant by load angle of an alternator? Upon what factors does the load angle depend?

2661


how we can calcultae the short circuit level for bus bar

1836