How much current can 11KV line carry? What are the
formulae used to calculate current across both side of
transformer? Moreover I need to know can I connect 33KV
line with transformer of 1600KVA? Details are: V=415,
Pf= .9
Answer Posted / arulkumaran
KW = KVA*PF
KW = 1600*0.9
KW = 1440
11KV PRIMARY CURRENT=
KW = 1.732*KV*I*PF root(3) = 1.732
1440 = 1.732*11*I*0.9
1440/1.732*11*0.9 = I
I = 83.98 AMPERE
415V SECONDRY CURRENT=
WATTS = 1.732*V*I*PF
1440000 = 1.732*415*I*0.9
I = 2226 AMPERE
| Is This Answer Correct ? | 80 Yes | 20 No |
Post New Answer View All Answers
How much load can be taken for chiller from 1500 kva transformer
IF I KNOW THE AREA OF CROSS SECTION OFTHE WIRE , WATTAGE OF THE LOAD ,VOLTAGE SUPPLY WHAT IM GIVING TO THE LOAD AND ALSO POWER FACTOR OF LOAD ....... SO GIVE ME FOR WHAT AMOUNT OF CURRENT I SHOULD USE WHICH TYPE OF CABLE?
Give atleast 20 alternating current apparatus and devices.
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
how we decide the require size is this for a known current at fuu load?
Explain what cmos is and its benefits?
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?
-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.
how to check avr of dg set of 125kva
How to size fuse? How to size MCB?
pls,send the previous year written test questions.
how to choose cable size with respect to load? how to convert cable size in mm2 to sq.mm?
at what base you will tell the direction of rotation of dc motors and generators?
In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?
Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.