Answer Posted / aftab ahmed mazari
Following procedure should be done for control valve
calibration.
Suppose it is spring loaded and direct action.(Direct
action means at top of diapgargm signal and with the
increase of signal, stem will move downwards or the stem
will extend).Also valve is signal to close. Check its Bench
Set. Suppose it is 6 to 21 PSI.
1. Set pressure regulator of positioner at about 30 PSI.
2. Apply 3 PSI (4 mA if positioner is smart or electronics)
signal to Positioner.Gradullay increase signal. Note the
movement of stem.
3. Apply 6 (8 mA),9 PSI (12 mA), 12 PSI (16 mA) and 15 PSI
(20 mA) signal. Valve stem should move accordingly and
indicator must show 25%,50%,75% and 100%.
4. If error, remove it from zero and span of positioner.
5. If facing any error problem, give signal 50% and then
remove error. Rest will be ok automatically.
6. Suppose valve is normally closed and at any vent service
and signal to close as I mentioned earlier, then make shut
close of valve at 14.5, or 14.7 PSI. Valve may start
closing at 2.75PSI.
7. If valve is at control operation, like level, pressure
etc, then calibrate it accurately.No need to calibrate it
at 2.75 and 14.5 PSI.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 31 Yes | 3 No |
Post New Answer View All Answers
How to Calibrate Vortex Flow transmitter in field
What is cut off relay? And why use in PLC and DCS?
what would be the minimum flow rate that we can measure on rotameter..?
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
what is diffrance between FF & SMART, explain with difination
Manipulation of dead wt. tester double piston type.
How to check vortex flow meter is in good condition while we do not having calibration setup?
Whether the DI, DOs shields can be connected with Analog Input Shield Earthpit?
How a conductivity sensor & analyzer work at boiler, whats the principle & science is beyond this,How conductivity sensor sence & convert signal & move toward analyzer & analyzer show reading in percent? also what is temperature compensate option in conductivity analyzer
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
what about your moleg in pogrees with company
How to calibrate the flow transmitter
please send me some question papers of HPCL aptitude test ?? please send it to bipinb.28@gmail.com ...
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
what are the definitions of input, output, command & signal according to instruments controlled by PLC using DCS System?