What is the right procedure for adjusting the gap voltage
of bently nevada vibration sensor?
Answer Posted / rana mujahid
first check all the physical checks like,prob material is
correct for service,cable length is proper accroding to
proximeter,termination,supply is proper(-24vdc),etc..
after this connect volt meter with proximeter b/w out and com.
and try to adjust exact -10vdc but -9.5 to -10.5 are ok just
configured in systm.
| Is This Answer Correct ? | 7 Yes | 0 No |