i install a DP transmitter of Faugi on drum level of boiler
but i face a problem in it when i engergize the transmitter
the meter shows 0 or 100% no variation in it.the distance
of two points is 19.5 inches, i am in trouble please
suggest me what can i do it's very urgent Please reply me
as soon as possible
Best regards
ikraam haider
Answer Posted / r.murugan
Dear haider
your transmitter calibration is perfect before charging the tramsmitter you have to fill the water in the condensing pot at low side of the tranmitter
boiler is shutdown condition please confirm DRUM VENT ISOLATION VALVES ARE OPEN
IF DRUM VENT ISOLATION VALVES ARE CLOSE YOU WILL NOT GET CORRECT READING
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Isometric drawings are generated during _________________ phase of a project
Gas equation
Explain about safety integrated level protection? . How it was differ from other protections ?
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
How can i copy program (parameter) from mm440 (V.F.D.) by using BOP?
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
hi sir yhis is zahid ali i am preparing for the jspl at oct.4.please send me the recently updated sample paper.
What is standard procedure of manual mapping in Radar type level transmitter?
what is vibration a part of proceess variable? if vibration is a part variables then how we minimize the actual vibration on machine on load,? vision of instrumentation contrl plz ans me IPGDL interview question
the 3 most common transmitter protocol being in refinery or qatar gas and aramco.
what are the definitions of input, output, command & signal according to instruments controlled by PLC using DCS System?
Explain bernoulli’s theorem. State its application.
How to change dcs card in online. (Dsc is maxdna)
Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com
What is the use of single seated valve?