If the maximum demand is 120 KVA in a building, then what is
the Current taken according to load given ? Formula for it ?
Answer Posted / jose
120 kva means you have to supply 3 phase load.
3 phase load with 415 v and unity pf can take a current
according to eqn kva=1.732*Kv*I
I=120*1000/(415*1)=290 A appr
| Is This Answer Correct ? | 6 Yes | 0 No |