Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is pf. how to calculate capacitor bank value to
maintain unity pf.

Answer Posted / shashikant

CALCULATIONS AND TABLES

Calculation and selection of required capacitor rating

Qc = P * {tan [acos (pf1)] - tan [ acos (pf2)]}

Qc = required capacitor output (kVAr)
pf1 = actual power factor
pf2 = target power factor
P = real power (kW)

The table below shows the values for typical power factors
in accordance with the above formula


TARGET POWER FACTOR
0.7 0.75 0.8 0.85 0.9 0.92 0.94 0.96 0.98 1
Actual Power Factor
0,40 1.27 1.41 1.54 1.67 1.81 1.87 1.93 2 2.09 2.29
0,45 0.96 1.1 1.23 1.36 1.5 1.56 1.62 1.69 1.78 1.98
0.50 0.71 0.85 0.98 1.11 1.25 1.31 1.37 1.44 1.53 1.73
0,55 0.5 0.64 0.77 0.9 1.03 1.09 1.16 1.23 1.32 1.52
0,60 0.31 0.45 0.58 0.71 0.85 0.91 0.97 1.04 1.13 1.33
0,65 0.15 0.29 0.42 0.55 0.68 0.74 0.81 0.88 0.97 1.17
0,70 0 0.14 0.27 0.4 0.54 0.59 0.66 0.73 0.82 1.02
0.75 0 0.13 0.26 0.4 0.46 0.52 0.59 0.68 0.88
0,80 0 0.13 0.27 0.32 0.39 0.46 0.55 0.75
0.85 0 0.14 0.19 0.26 0.33 0.42 0.62
0,90 0 0.06 0.12 0.19 0.28 0.48


The required capacitor output may be calculated as follows:
select the factor (matching point of actual and target
power factor) k
calculate the required capacitor rating with the formula:

Qc = k * P

Example:
actual power factor = 0.70, target power factor = 0.96,
real power = P = 500kW,

Qc = k * P = 0.73 * 500kW = 365 kVAR

Is This Answer Correct ?    3 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

and gate circuit diagram,amplifier circuit diagram

2068


i am going to attaned the engineer (disign)iterview at HAL please give me duid line

2282


any one can explain the stages of a knee point which is taken during ct magnetising curve.

1783


Where can I get CPWD electrical specifications & Shedule of rates? Please help me

2257


How would you calculate power loss in a resistor?

1074


what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?

2184


Can clean earth cable be considered as low current cable

1967


Why lose 1 phase voltage in 33kv to 415v stepdown transformer

1742


Batteries. What is the difference between Lead and Nickel batteries ?

2209


What is a difference between indoor transformer and outdoor transformer of same rating

5823


Dear friends, i would like to know that what is the exact function of 'exciter winding' & 'aux winding' in Alternator?

2009


hi guys please tell me the procedure for mesuring the coil resistance of 3ph induction motor?

1897


Is there any abbrevation for STUB in Stub bus protection

1939


Whether amorphous core transformer is commercialized or not:Name of company making amorphous core transformer and what are different rating?

1799


i have install 750 kva distribution transformer at my site and want to do neutral earthing. what calculations should i follow to determine earthing conductor material and size?

2060