How to calculated capacitor rating both HT
Answer Posted / rajib
KVAR=KW(tan@1-tan@2)
Where, @1= system power factor, @2= desire power factor
For example. 500KW motor has system power factor 0.8 and we want to improve it 0.95
tan@1=tan cos-1(.8)=0.75
tan@2=tan cos-1(.95)=0.3287
KVAR=500(0.75-0.3287)=210.65=210KVAR
and so on
Is This Answer Correct ? | 19 Yes | 0 No |
Post New Answer View All Answers
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.
Show the schematic arrangement of diesel power station layout and give its principle of operation.
hi frds, i m electrical engineer.can i get cdr for electrical engineer if u have then send me on my mail id its jayesh_ee88@yahoo.com.please help me frds
Explain the working of any one cutting machine
After synchronization with grid what is the demand value QKVAR and how we will maintain that?
How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.
How will you utilise electrical power? You can start from the generating station.
Bimetal strip used in overload relay what is that,which types of material used for that & percentage.
relation between power station capacity and voltage level?
how mass curve differs from hydrograph.
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
Is there chopping current in resistive circuit
why current is constant on d.c?
What is a parabolic signal?
1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?