How to calculated capacitor rating both HT
Answer Posted / rajib
KVAR=KW(tan@1-tan@2)
Where, @1= system power factor, @2= desire power factor
For example. 500KW motor has system power factor 0.8 and we want to improve it 0.95
tan@1=tan cos-1(.8)=0.75
tan@2=tan cos-1(.95)=0.3287
KVAR=500(0.75-0.3287)=210.65=210KVAR
and so on
| Is This Answer Correct ? | 20 Yes | 0 No |
Post New Answer View All Answers
is there any current and voltage drop on liquid resistance starter water/soda tank ?
hi friends i m from electrical branch and seeking for tech. + apti. both papers of hpcl plz get it available as soon as possible
How can calculate the rating of a servo stabilizer for given a specific load
Dear sir, I completed DECE In the year 1995.Now i am working in a private company from last 10 years as an Electrical supervisor.The company having a 1000 KVA transformer.Now i try to apply "C" Licence. I am eligible or not.If not eligible,pls give solution.
Draw the circuit of clapp oscillator?
What facility we get after CT secondary earthing and how?
Given a collection of points P in the plane, a 1-set is a point in P that can be separated from the rest by a line; i.e. the point lies on one side of the line while the others lie on the other side. The number of 1-sets of P is denoted by n1(P). The maximum value of n1(P) over all configurations P of 19 points in the plane is 18
What do you mean by a current transformer?
What is shutdown of electrical sub station?
What is the minimum IR value of HT/ LT cable? Pls post separetely!!!!!
A d.c. Shunt motor is found suitable to drive fans because they require?
what are all types of cross section in AC cables?
i m in need of current rating chart of heavy duty pvc/xlpe, cu/al cables. can somebody provide me? if yes, plz send me at ashish_patel111@yahoo.com
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?