how can you set a zero and span of transmitter?
Answer Posted / bunny
First give the LRV(Lower Range Value)to the transmitter.If
it is an electronic transmitter,the o/p should be 4mA.If it
is a pneumatic transmitter,the o/p should be 3psi.If we are
not getting the above values,adjust the zero screw in the
transmitter by a screw driver,till we are getting 4mA or
3psi.This is called zero adjustment.Simillarly give URV
(Upper Range Value) to the transmitter.So the output for
electronic and pneumatic transmitters should be 20mA and
15psi respectively.If we are not getting it,adjust the span
screw in the transmitter by a screw driver till we are
getting 20mA or 15psi.This is called span adjustment.
LRV & URV:Suppose the range of a transmiter is 0-30psi.Then
LRV=0psi & URV=30psi.
| Is This Answer Correct ? | 23 Yes | 0 No |
Post New Answer View All Answers
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
What is the use of double seated valve?
which type inter lock use in petrochemical refinery,and oil & gas?
Why mmwc unit is used?
Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....
What is difference between differential pressure & delta pressure?
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
How earthing can be checked????
why we us isolation barrier in hazardous area how it works to protect the area and please clarify its current flow.
I want measure the volumetric flow of gas in waste heat recovery Boiler?Tell me how and which type of instruments required. Plz mail me:naba02222@gmail.com Sam please post the answer .
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?
What is the working principle of the magnetic meter?
Why trim span ? How?
How would you choose differential range?
How many types of sensor