which fault current is maximum: 3 phase short circuit, LG,
LL or LLG?? why??
in one of the problems that i have solved, 3 phase short
circuit current on an unloaded generator came out to be
less than the LG fault current. can anybody please explain
why.
Answer Posted / dr rajan
It is always the 3 phase bolted fault. Check your problem
again. You may have made a mistake. Why 3Ph fault current is
high?
When all phases are grounded or shorted, the impedance is just
let us say X in each phase leading to V/X x 3 times. where as
when you have LG, you will include the line impedance in
series with X, equals X+xL, which is more than X on 3Ph short
ckt. When you divide V/(X+xL) what will you have???? More
current or less current???????
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
How much load can be taken for chiller from 1500 kva transformer
Best way to measure the Soil resistance of rocky soil, three probe method and four probe method
Define peak time.
WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION
How maesure earth neutral value & how much maximum value value required in between earth & neutral.
design a 3 bit synchronous and asynchronous counter using T- flipflop
How to find ampere on ht side for selection of cable size ???
what is meant by IGBT how they differ from tyristor ?
what is the ground fault relay,which purpose it will be use,clearly tell me plz
What is your acheivements
What is PEC??Applications........
what is effect of 5amp fuse on 2mva pry protection of transformer
what is the star delta connetion and how can do it a three phase motor with control witing with picture
why the frequency and voltage in india is 230v and 50HZ. when compared to USA say 110v and 60 HZ.
how to discharge 3 phase power factor correction capacitors