which fault current is maximum: 3 phase short circuit, LG,
LL or LLG?? why??
in one of the problems that i have solved, 3 phase short
circuit current on an unloaded generator came out to be
less than the LG fault current. can anybody please explain
why.
Answer Posted / dr rajan
It is always the 3 phase bolted fault. Check your problem
again. You may have made a mistake. Why 3Ph fault current is
high?
When all phases are grounded or shorted, the impedance is just
let us say X in each phase leading to V/X x 3 times. where as
when you have LG, you will include the line impedance in
series with X, equals X+xL, which is more than X on 3Ph short
ckt. When you divide V/(X+xL) what will you have???? More
current or less current???????
Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
What is Surge Capacitor? Why it is use in Generator Circuit Breaker?
what is the chiller and working principal
The screw thread commonly used for transmission of motion is one of the following types of threads
What is signal flow graph?
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
all details of DG UPS HVAC
it is possible to measurement of tension of slipring induction motor(SRIM)carbon brushes, any maesuring instruments are available in the markets.
types of central Air conditioner plant?
What happen if we apply square wave or traiangular waveform voltage to the transformer primary winding instead of sinusoidal wave?
what is per unit calculation?looking for simple and strong explanation thk u
If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?
how much leakage current is allowed in MC61A L&T make relay?
dc supply given to dc generator winding.how is possible? my knowledge is saying the winding will burn. please reply.
how to check regenerative load in drived motor
How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?