which fault current is maximum: 3 phase short circuit, LG,
LL or LLG?? why??
in one of the problems that i have solved, 3 phase short
circuit current on an unloaded generator came out to be
less than the LG fault current. can anybody please explain
why.
Answer Posted / dr rajan
It is always the 3 phase bolted fault. Check your problem
again. You may have made a mistake. Why 3Ph fault current is
high?
When all phases are grounded or shorted, the impedance is just
let us say X in each phase leading to V/X x 3 times. where as
when you have LG, you will include the line impedance in
series with X, equals X+xL, which is more than X on 3Ph short
ckt. When you divide V/(X+xL) what will you have???? More
current or less current???????
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
Installation resistance for whole installation of 16 kva & 25 KVA DTRA a) Between each conductor b) between conductor to earth c) installation resistance for each apparatus, each conductor to earth d) earth resistance for the system of earthing
A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is
how external lighting design? please give examples?
how brushed dc motor operating ?
why not starting switch first connect in direct on line starter?????
An ELHNC 80amp 240v 30mA RCD is tripping periodically, every 30 - 180 seconds is it safe to disconnect the protection circuit?
Define early construction of human being
hi frnz,can somebody give me any project work? i am a 2nd year student & interested in practical works...plz give me some projects
what is the difference between surge protection capacitor and surge arrestor
What do you mean by ratio correction factor of instrument transformer?
what is the solution for meger test failed the MV cable?
what is the eight bit unit?
plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in
Explain what is use of lockout relay in ht voltage?