Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Sir we have 12.5 MVA(110/11KV) transformer (Y-Y)
connected,which tripped showing earth fault,when we charged
transformer it stood OK ,but on connecting 11 KV feeders it
tripped showing earth fault.our service engineers found that
the B phase and R phase phase connecting to neutral broken
from HV OLTC(on load tap changer),and R phase and Neutral is
ok.Dissolved gas analysis shows that accetline content is
high,tan delta value is 12.My dout is it is an internal
fault of transformer,why REF or diffrential relay is not
acted?

Answer Posted / k.prakashchandra

REF relay does not act as the unbalanced current is equal to
NCT current in all respects. And for diff relay, it also
does not act as the corresponding ct currents in HT and
sides for each phase are equal.If there is current in only
one phase ,EFR will trip as current's return path is through
the EFR.But why there is current in the single good phase as
all dist Trs are delta/ star connected ? May be due to star
connected line capacitors or dist trs/loads are also star
connected with neutrals earthed.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?

2063


what happen if drive input fail momentry at 48.5 HZ frequency?

1859


how ct burden,magnetising current,ratio and knee point voltage are related & derived

2148


what are the 4 rules to start the motor?

2047


How can ou verify the size of conductor 50Sq.mm ACSR

1888


What is frantic effect?

1198


What should be the protection scheme for a 15kw, 3-phase motor working in a lathe machine.

2016


what is x'mer ,isolation x'mer & yltra-isolation x'mer?????

2380


specify the inbuilt protections in DG

2016


Define availability (operational)?

1101


Why we use Electrical energy rather than any other type of energy, mostly? Explain behavior of open secondary CT and short circuited secondary PT in energized condition?

1821


how to control the speed to switched reluctance motor

1888


if voltage bt phase & nutral is 38v in a panel board . whats the root cause.

2265


A Question Like A Wire Is Wound Whose Resistance Is Some 132. 44647 Ohms. If A Voltage Of 30 mv, 296 Ma Current Is Applied To It What Is The Resistance.

1020


why we use two slope(differential & restraining) in differential relay.but in busbar protection differential we are using only one slope?please explain

2194