hello dear
i have faced problem in drum level transmitter.
the problem is when i engrize the meter meter shows 100%
but the actual level 40 or something plz suggest me
Answer Posted / aftab ahmed mazari
It seems that transmitter low side leg is leaking, or low
side is not being fully condensing.
Please chck low leg fittings, connections and if ok. Then
check transmitter high side and low side pressures with the
help of digital pressure gauge. May be transmitter low side
any problem.When you calibrate tranmitter workshop, also
apply pressure to its low side, indication should go down
to confirm that low side is ok.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
1.what is the power consumption of three element drum level control in sugar industries? 2.how to reduce that?
what is the procedure of belt scale calibration?
the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove
Differentiate between ultrasonic flowmeter and radar type flow meter
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
What is the purpose of bypass valve across AS valve.
Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.
What is compensation for flow ? Why we use compensation ? What are the factors of different compensation ? We not use then what problems may happen ?
In turbine, what does term CDP, NI, NH, HSSOC, means
Positioner usage.
What is cut off relay? And why use in PLC and DCS?
How RAL(Rotary air lock)works in cement industry?
Make Heater Process Logic.
What are the maximum packet size of: a) HART b) Profibus DP c)Profibus PA d) DeviceNet e) Foundation Fieldbus