Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Sir We have a REF relay connected to 10MVA(Y-Y) Transformer.on
External earth fault REF relay trips along with earth fault
relay.The REF relay has no complant as we tested relay.Why is
it happening?

Answer Posted / shariff

REF relay shold not operate otherthan its zone of operation
i.e 11kV REFR zone is from 11kV trf busings to 11kV CT
(incomer) and some times PT also if PT is before CT. It is
a mal function only and it can be any of the following.
1) Check the 11kV NCT wiring it may be loose/ got cut in
the NCT wiring box in the yard.
2) The 11kV incomer CT wiring may be loose/ got cut etc.
3) Check the 11kV PT primary resistance it may notbe equal.

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What type of a DC motor would you use for a lift?

1124


In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?

3194


i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.

1914


explain me the relation between torque, frequency,speed,voltage and current in the 3 phase induction motor?

2302


Let me know that how i calculate the alternator sub tranciant reactance and tranciant reactance.

2698


how slip power recovery system work

3074


How to calculate the current of Highpressure Mercury Vapour Lamp?what is the basis?whether we have to consider power factor or not?

2225


i karmveer bharti persuing b.tech . plz send me syllabus and name of reference books. for preparation of section eng.

2186


why does the magnetic balance tests at transformer?

1998


Dear All we are having a problem in G120 BOP showing alarm A0503, F0052, F0060 we can not remove fault alarm ,Please any body help us. kowsar

1920


Enlist four components of electrive drives.

1885


For electrical designers what are the standard should know? i want learn about this standards. how to get information/reference. anybody help in this regards please.

2202


what is the reactance,capacitance & impedence electrical armoured & unarmored Cables.

2260


In Air circuit breaker LSIG protection unit is used. Without fault in cables (2 runs 3Cx150Sq.mm Copper, 1Kv grade, XPLE armored cable IR value is more than 550Mohm @ 500V Megger) and load section Long time Overcurrent protection is triggers and trips the unit. We changed LSIG protection with new factory tested unit. Even then fault is persisting. Please suggest the possible causes

860


Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1869