Answer Posted / aftab ahmed mazari
Differential pressure switch has two sensing ports. Hi and
Lo, Suppose set point of differential pressure switch is
30 PSI. Connect the pressure source at hi side of switch.
Leave Lo side (No any connection or any supply to low side)
Connect multimeter at switch terminals. Apply pressure at
high side. When pressure will reach 30 PSI, Switch will
operate and will change its contacts and also will be
indication at meter.
Suppose switch Low side is faulty, then apply 30 PSI at
High side and also apply low side pressure (5 to 10 PSI),
switch contacts should change, which indicate switch is
working.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 21 Yes | 2 No |
Post New Answer View All Answers
Senior engineer's please help me, what is Loop Checking and Loop test? and write difference also? soon urgent
What are primary elements of measuring pressure?
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
please can any one tell me clearly about pid tuning i am confusing about this .how to tune pid easly?
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
Tell about your IFFCO plant visit.
WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN
Define cryogenic?
what is the procedure of belt scale calibration?
What is the main difference between Cavitation and Flashing?
what is the diffrence between pressure safety valve & pressure relief valve....pls
How to fix back the valve actuator stem
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?
what is the responsibility of an instrument commissioning supervisor