Answer Posted / aftab ahmed mazari
Differential pressure switch has two sensing ports. Hi and
Lo, Suppose set point of differential pressure switch is
30 PSI. Connect the pressure source at hi side of switch.
Leave Lo side (No any connection or any supply to low side)
Connect multimeter at switch terminals. Apply pressure at
high side. When pressure will reach 30 PSI, Switch will
operate and will change its contacts and also will be
indication at meter.
Suppose switch Low side is faulty, then apply 30 PSI at
High side and also apply low side pressure (5 to 10 PSI),
switch contacts should change, which indicate switch is
working.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 21 Yes | 2 No |
Post New Answer View All Answers
Explain the key components of control loop?
What you mean by multi stage control vavles?
If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?
whatis range of marcury filled tempereture gague
selection criteria of control valve? and selection criteria of actuator explain in brief?
What are primary elements of measuring pressure?
Please tell me details about Sox,Nox,SWAS analyser????
Whether the DI, DOs shields can be connected with Analog Input Shield Earthpit?
how to calculate signal cable sizing? and multipair cable sizing??explain in brief?
Why do we floating DC in DC system.
give eg of how I/P is used in control loops
Explain the difference between plc and cnc?
What is the principle of capacitance type level transmitter?
What is stripper & spilitter ? Diffrence in this.?
in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.